Place of Origin: | China |
Hàng hiệu: | EuroKlimat |
Chứng nhận: | ISO9001, ISO14001, OHSAS18001, CRAA, CQC |
Model Number: | EKWD |
Minimum Order Quantity: | 1 pcs |
---|---|
Giá bán: | negotiable |
Packaging Details: | Plywood |
Delivery Time: | 10 working days after received your payment |
Payment Terms: | T/T or L/C |
Supply Ability: | 5,000pcs per month |
Tên sản phẩm: | Đơn vị thu hồi nhiệt đơn vị nguồn mặt đất bơm nhiệt làm mát nước nóng | Dung lượng làm lạnh (kW): | 76-153 |
---|---|---|---|
Công suất sưởi ấm (kW): | 79-159 | Nhiệt độ nước đi ra ngoài (° C): | 55 |
Lạnh: | R410a | Máy bơm nước: | Tùy chọn |
Công suất phục hồi nhiệt KW: | 68-137 | ||
Làm nổi bật: | air heat recovery unit,waste heat recovery unit |
Heat recovery unit modular ground source heat pump cooling heating hot water
Specifications
Basic modules | EKWD021CRDR/DV | EKWD032CRDR/DV | EKWD043CRDR/DV | |||
Underground circulation mode | Nominal Cooling Capacity | kW | 76 | 113 | 153 | |
Nominal Heating Capacity | kW | 79 | 115 | 159 | ||
Total Power of Nominal Cooling Capacity | kW | 13 | 20.4 | 27.2 | ||
Total Power of Nominal Heating Capacity | kW | 16.8 | 26.0 | 34.3 | ||
Water flow | Application side | m³/h | 13.1 | 19.4 | 26.3 | |
Heat source side | m³/h | 15.3 | 22.9 | 31.0 | ||
Heat Recovery Mode |
Nominal Cooling Capacity | kW | 67.7 | 102 | 137 | |
Nominal Heat Recovery Capacity | kW | 85 | 128 | 172 | ||
Total Nominal Power | kW | 17.3 | 26 | 35.0 | ||
Nominal water flow at the heat recovery side | m³/h | 14.6 | 22.0 | 29.6 | ||
Nominal water flow at the evaporation side | m³/h | 13.1 | 19.4 | 26.3 | ||
Water heater mode | Nominal Heating Capacity | kW | 72 | 109 | 146 | |
Total Nominal Power | kW | 20 | 30.6 | 41.0 | ||
Nominal water flow at the hot water side | m³/h | 14.6 | 22.0 | 29.6 | ||
Water flow at the heat source side (evaporation side) |
m³/h | 15.3 | 22.9 | 31.0 | ||
Water pressure drop |
Application side (air conditioner side) | kPa | 19 | 35 | 32 | |
Heat source side | kPa | 26 | 20 | 19 | ||
Heat exchanger type |
Application side (evaporator) | Plate | Shell-and-tube | |||
Heat source side (condenser) | Shell-and-tube | |||||
Recommended total pipe diameter |
Evaporator | mm | DN65 | DN65 | DN80 | |
Condenser | mm | DN65 | DN65 | DN80 | ||
Volume Adjustment | Steps | 2 | 3 | 4 | ||
Regulation mode | Fuzzy control | |||||
Compressor | Model | Fully hermetic volute | ||||
Lubricant | Mineral oil (SUNISO 3GS) | |||||
Refrigerant | Flow control method | Electronic expansion valve | ||||
Category | R22 | |||||
Dimensions | L x H x W | mm | 1647x1202x632 | 2247x1488x710 | ||
Unit weight | Net weight | kg | 452(517) | 703(818) | 887(1040) | |
Transportation weight | kg | 478(543) | 738(853) | 922(1075) |
Notes: Test conditions for the unit are as follows:
■ Test conditions for nominal cooling capacity: inlet chilled water temperature at the application side 12°C; outlet chilled water temperature at
the application side 7°C; inlet cooling water temperature at the heat source side 25°C; outlet chilled water temperature at the heat source
side 30°C.
■ Test conditions for nominal heating capacity: inlet/outlet water temperature at the application side 40/-°C, and rated water flow at the
application side for nominal cooling; inlet/outlet water temperature at the heat source side 7/-°C, and rated water flow at the heat source
side for nominal cooling.
■ Test conditions for the heat recovery mode: inlet/outlet water temperature at the heat recovery side 40/45°C; inlet/outlet chilled water
temperature at the application side 12/-°C, and rated water flow at the application side for nominal cooling.
■ Test conditions for the water heater mode: inlet/outlet water temperature at the hot water side (application side) 50/-°C, and rated water
flow at the heat recovery side for heat recovery conditions; inlet/outlet water temperature at the heat source side (evaporation side) 7/-°C;
rated water flow at the heat source side for nominal cooling.
■ Switching between the cooling, heating, water heater, and heat recovery modes is implemented through an external valve connected to
the water system. The unit provides a interface for controlling the electric valve.
■ The water main of the assembled unit needs to be made and mounted on site, and the diameter needs to comply with the design
specification.
■ The attached Y-shaped filter must be mounted at the water inlet of the evaporator of each unit.
■ The net weight in brackets indicates the weight of a dual-condenser heat recovery unit.
■ The cooling water and chilled water of the unit must be softened to avoid scaling in the heat exchanger.
■ The water pressure drop of the unit does not include resistance of any external water pipe or component.
■ Basic modules of the assembled unit are EKWD032CRQRM/S, EKWD043CRQRM/S, EKWD032CRQVM/S, and EKWD043CRQVM/S. A
unit may be formed by modules of the same model or different models.
■ Product specifications are subject to change due to upgrade without further notice.
More Efficient
The modular water source/geothermal unit supports applications in all conditions and can switch between multiple modes to fully meet user needs for cooling, heating, and hot water. With an innovative water system, the energy-saving unit delivers an EER as high as 5.7, provides higher energy efficiency when working at a partial workload, and saves energy by 50% compared with other systems after operation in a year.
More Comfortable
The unit is designed with a comprehensive water system and consists of efficient components carefully selected and designed for a low operation noise. The unit supports fuzzy volume regulation for a narrow range of temperature changes and quickly reaches the set temperature.
In addition, the unit provides hot water at a set temperature as high as 55°C quickly and steadily to meet requirements for comfortable hot water in all places.
More Reliable
With modular design, the unit starts step by step, reducing the shock on the grid, and maintenance of a single unit does not affect running of other units. In addition, the unit provides multiple built-in security protection functions, and supports intelligent and centralized control, facilitating daily management.
More Energy Saving
The leading-edge shell design allows the unit to be installed in an outdoor space such as terrace and rooftop without the need of a dedicated room. The unit delivers a long lifecycle and runs for long. Units may be installed in batches according to project progress. One water system that works in multiple modes saves investment on other devices such as heating and hot water supply devices, thereby saving the energy.
Convenient Model Selection
The 32RT and 43RT basic modules support free combination of master units and slave units to
from 1 to 16 units, providing as many as 153 solutions for a cooling capacity as high as 688RT.
Easy Switching
The unit sends control signals to valves of the water system to easily switch between the water
source/geothermal heat pump mode, heat recovery mode, and water heater mode, meeting requirements for cooling, heating, and hot water around the clock.
Variable Water Flow Design
The unit easily implements variable primary flow pumping, which helps the central air conditioning system save energy by 30%.
Easy Transportation
The modular design allows transportation by using elevators and manual forklifts and eliminates the need for hoisting.
Easy Installation
The modular design allows units to be moved separately and assembled, facilitating installation work.
Người liên hệ: Mr. LENG Zhengliang
Tel: +86 13828797702